Current transformer secondary open circuit - Database & Sql Blog Articles

Brand AVX TPSE226M035R0125 Low impedance tantalum capacitor AVX 22
Electronic scale crystal oscillator 3.2*2.5mm 3225 16M (16.000MHZ) 12PF 10PPM 20PPM 30PPM
Probe current voltage pin 420*4450 head diameter 5.0 over current current and voltage pin
inductance

The reasons for generating a secondary open circuit of the current transformer are as follows:
(1) Due to the defects in the structure and quality of the test terminal in the AC current loop, the screw and the copper plate screw hole are in poor contact during operation, resulting in an open circuit.
(2) Since the glue wood of the test terminal pressure plate in the current loop is too long, the metal piece of the rotary terminal is not pressed on the metal piece of the pressure plate, and is mistakenly pressed on the bakelite sleeve, thereby causing an open circuit.
(3) Mistakes in the work of the repair personnel, such as forgetting to connect the internal connector of the relay and fail to find it during acceptance.
(4) The secondary wire terminal fitting is not tightly pressed, and when the current in the circuit is large, the heat is blown or oxidized to cause an open circuit.
(5) The outdoor terminal box and junction box are damp, and the terminal screws and gaskets are rusted too much, resulting in an open circuit.

24V Power Supply

24v power supply, the current range is 2A-9.2A, the max power is 220w. We also can meet your specific requirement of the prodcuts.The material of this product is PC+ABS. All condition of our product is 100% brand new.

Our products built with input/output overvoltage protection, input/output overcurrent protection, over temperature protection, over power protection and short circuit protection. You can send more details of this product, so that we can offer best service to you!


24V Power Supply,24V Pc Power Supply,24V Dc Power Supply ,24V Power Supply For Pc

Shenzhen Waweis Technology Co., Ltd. , https://www.huaweishiadapter.com